Type 1 vs Type 2 Hood: Differences, Which You Need and Ventless Options
Type 1 vs Type 2 hoods: grease vs heat and moisture, which appliances need which, how ventless listings work, and what to check on a used hood.
A Type 1 hood (written "Type I" in the codes) collects grease vapors and smoke and is equipped with a fire suppression system. A Type 2 hood ("Type II") handles steam, heat, odors and products of combustion from equipment that doesn't produce grease or smoke. Under the 2021 International Mechanical Code (IMC), if any appliance under a hood requires Type I, the hood must be Type I.
Your local authority having jurisdiction, meaning your mechanical and fire officials, decides what your kitchen needs. This guide is general information, not engineering, legal or code advice.
| Type I (Type 1) | Type II (Type 2) | |
|---|---|---|
| What it handles | Grease vapors and smoke | Steam, vapor, heat, odors and products of combustion |
| How makers describe it | Grease hood | For condensation or heat removal |
| Typical appliances | Fryers, griddles, open-burner ranges, under-fired broilers, wok ranges | Dishwashers, steamers, steam-jacketed kettles, pasta cookers, some ovens |
| Fire suppression | Approved automatic system required | Not part of the IMC definition |
| Duct | Grease duct: steel of at least No. 16 gage or stainless of at least No. 18, with an exception for certain factory-built products, plus a leakage test before use or concealment | Rigid metal duct built under IMC Chapter 6 |
| Termination above a roof | At least 40 inches above the roof surface | At least 30 inches above the roof surface |
| Can it stand in for the other? | Yes, it can be installed where Type II is required, but the whole system must then meet Type I requirements | No, not where any appliance under the hood requires Type I |
The table summarizes the 2021 IMC, which your jurisdiction may have amended or may not use at all.
What does IMC Section 507 say?
We read the 2021 and 2024 editions on the International Code Council's site. In the 2021 edition:
- Type I: Required where appliances produce grease or smoke, and over medium-duty, heavy-duty and extra-heavy-duty appliances (507.2).
- Type II: Required above dishwashers and appliances that produce heat or moisture without grease or smoke, unless those loads are handled through the HVAC design or a separate removal system. Also required above appliances that produce products of combustion without grease or smoke (507.3).
- No Type II: Spaces with appliances that don't need a Type II hood still need exhaust at 0.70 cfm per square foot, counting each appliance as at least 100 square feet (507.3).
- The whole system follows: Where a Type I hood is installed, the hood, ducts, exhaust equipment and makeup air must meet Sections 506 through 509 (507.1).
- Exceptions: These cover certain listed factory-built hoods, recirculating systems, down-draft appliances and smoker ovens (507.1). Another covers electric appliances with testing agency documentation showing 5 mg/m³ or less of grease at 500 cfm under UL 710B (507.2).
The 2024 edition reorganizes some of this. It names light-duty appliances in the Type II section. It lists situations where no hood is required, including electric appliances listed to UL 197 for reduced grease emissions. It also lets a Type I hood serve only Type II appliances without fire suppression or grease filters, if the installation otherwise meets Type I requirements.
Edition matters because adoption is local:
- Tucson's hood chart is based on the 2018 IMC.
- A 2021 Pittsburgh bulletin cites the 2015 IMC and says it continues to apply under later editions until the city modifies or rescinds it.
- Minnesota's rule, as published by Cornell's Legal Information Institute, deletes IMC Sections 507.1 through 507.6.1. Its replacements point to NFPA 96 and ASHRAE 154 for Type I hoods.
- San Francisco's 2026 guidance works from the California Mechanical Code.
Ask your building department which code and edition apply before you buy anything.
What does NFPA 96 cover?
NFPA 96 is the National Fire Protection Association's standard for ventilation control and fire protection of commercial cooking operations. NFPA describes it as fire safety requirements meant to reduce the fire hazard of public and private commercial cooking. NFPA's page lists 2027 as the current edition, though your jurisdiction may enforce an older one. San Francisco's 2026 sheet, for example, references the 2021 edition.
NFPA sells the standard and offers a free-access view, but we did not review its full text. What follows comes from a 2021 blog on NFPA's site about dine-in restaurants with an occupant load of 50 or more. It is an overview and doesn't necessarily represent NFPA's official position:
- Cooking processes that produce grease-laden vapors need ventilation and a fire extinguishing system.
- Those extinguishing systems must be listed to UL 300 or an equivalent standard.
- Extinguishing systems are maintained at least every six months.
- Hoods are inspected for grease buildup, typically twice a year for most restaurants depending on cooking type and volume, and cleaned when buildup is found.
Which equipment typically needs which hood?
The IMC sorts appliances by duty class. Tucson's chart shows how one city applied that to specific equipment under the 2018 IMC. It is an example, not a rule for your location.
| Appliance | Duty class (2021 IMC definitions) | Tucson chart (2018 IMC basis) |
|---|---|---|
| Solid-fuel appliances | Extra-heavy | Type I |
| Open-burner gas ranges, wok ranges, under-fired broilers, salamanders | Heavy | Type I |
| Fryers, griddles, hot-top ranges, tilting skillets | Medium | Type I |
| Conveyor pizza ovens | Medium | Type I |
| Deck pizza ovens, cheesemelters | Light | Type I |
| Combination convection/steamer ovens | Light | Marked for both Type I and Type II |
| Convection and standard ovens | Light | Type II; Type I for electric convection and standard ovens that produce grease and smoke |
| Steamers, steam-jacketed kettles, pasta cookers | Light | Type II |
| Countertop conveyor ovens listed to UL 710B | Light (countertop conveyorized baking/finishing) | No hood, with exhaust conditions |
| Coffee makers, steam tables, hot dog cookers, toasters | Not named in the definitions | No hood, with exhaust and HVAC conditions |
Light duty doesn't automatically mean Type II. The menu matters too, since the 2021 code's trigger is whether cooking produces grease or smoke. Residential appliances aren't automatically exempt either: the IMC ties the hood to the appliance and process when a domestic appliance is used commercially. Pittsburgh's bulletin excludes restaurants and other commercial food service establishments, but it sorts domestic appliances in other spaces by type of space and occupant load.
What do "ventless" and UL 710B actually mean?
"Ventless" isn't the name of a UL category in the guide information we reviewed. Two different categories come up, and the difference affects fire protection.
| Recirculating system | Reduced-emission appliance | |
|---|---|---|
| UL category | KNKG (complete system) or YZCT (hood for specified appliances) | KNLZ |
| Standard named | UL 710B | UL 197 |
| How it works | Fan, hood and filters return filtered air to the room | Integral feature limits grease-laden air; TurboChef describes a catalytic converter |
| Fire extinguishing | Integrated and evaluated with the appliance | None integral; ask the authority about a field-installed system |
UL's 2006 article on recirculating hoods describes an emissions test based on EPA Test Method 202. Grease-laden effluent can't exceed an average of 5 mg/m³ during an eight-hour cooking test. UL notes the article may not reflect later changes. UL guide information reproduced in San Francisco's 2026 sheet applies the same 5 mg/m³ limit and EPA-202 method to KNLZ appliances.
A listing doesn't end the review:
- The 2021 IMC treats a room with a UL 710B system as a kitchen for ventilation, counting each appliance as at least 100 square feet.
- UL says the building must still provide enough ventilation, heating and cooling.
- UL guide information says KNKG and KNLZ appliances aren't intended for connection to a ducted exhaust system.
- San Francisco's interpretation requires a UL 300 listed extinguishing system for KNLZ appliances without integral suppression. Another jurisdiction may decide differently.
Not every ventless product suits every appliance. CaptiveAire says its RH recirculating hood is a Type II hood for electric appliances such as ovens, conveyor ovens and rotisseries, and isn't for gas or grease-producing equipment. Its manual says that hood is ETL listed to UL-710B and EPA Method 202, so the mark on a listed unit may be ETL rather than UL. CaptiveAire also says second- and third-stage filters need quarterly checks and replacement, which is a running cost to price in.
Do TurboChef ventless ovens need a hood?
TurboChef says its ventless ovens can be installed without a Type I or Type II hood when its recommendations are followed. It cites the 2006, 2009 and 2012 IMC, NFPA 96, NFPA 101, EPA 202 and UL KNLZ. It doesn't mention UL 710B, and those IMC editions are older than the ones discussed above. The limits TurboChef states:
- Ventless operation isn't supported for fatty raw proteins, such as bone-in skin-on chicken, raw hamburger and fat-laden steaks.
- Its submittal steps include working out whether the health agency, building agency or both need notice. They also call for an HVAC analysis and your menu.
- The High h Conveyor 2020 and 2620 may need added fire suppression at local discretion.
- In TurboChef's words, "Ultimate ventless allowance is dependent upon AHJ approval," and it notes that some jurisdictions may not recognize the certification.
For a used oven, confirm the exact model against TurboChef's submittal package. Then take that package and your menu to the local authority before you pay.
Why isn't a used hood plug-and-play?
A hood is one part of a system designed around a specific cook line and building.
- Sizing and rating: The IMC requires a Type I label showing minimum exhaust flow per linear foot. Greenheck says its label also covers allowable cooking surface temperatures and overhang requirements. Published minimums vary by style: CaptiveAire lists 150 to 200 cfm per foot for its BD-2 backshelf hood and 346 to 475 for its NDI double-island hood, depending on cooking temperature.
- Mixed lines: Where the 2021 IMC's capacity section applies, the heaviest appliance sets the rate for the whole hood. A Type I hood over extra-heavy-duty appliances can't also cover lighter ones.
- Makeup air: The IMC calls for makeup air approximately equal to exhaust, and for design plans to show the air balance. Greenheck warns that positive pressure in a kitchen can hurt hood performance and push odors into the dining area.
- Fire suppression: NFPA's blog warns that these systems are designed for the original equipment, so changing the equipment without analysis could mean a failure to extinguish a fire. Greenheck says a certified fire system installer should install or finish, test and certify the system. A service tag shows history at the old site, not fitness for your line.
- Duct and clearances: A Type I hood needs its grease duct, and the permit holder is responsible for the leakage test. The IMC sets 18 inches of clearance to combustibles, with exceptions. A hood that was cut down for removal raises questions for the manufacturer and inspector.
- Installer and inspection: Greenheck says only qualified personnel should install its hoods and tells installers to check clearances with the authority first. Ask your department what plans and inspections it requires.
What should you ask a seller of a used hood?
Food Service Surplus connects buyers and sellers. It doesn't sell, buy, inspect, test, ship or guarantee equipment, so get these answers from the seller:
- Is it Type I or Type II? What are the manufacturer, model and serial number?
- Can you send a clear photo of the label inside the hood, showing listing, temperature rating and minimum exhaust?
- What are the length, depth and height, and what appliances ran under it?
- Does the sale include filters, the fire suppression system, fan, curb, controls or makeup air unit?
- When was the fire system last serviced, and do you have records?
- Has the hood been cut, patched or modified? How was the duct disconnected?
- Who handles removal, and at whose cost?
- For ventless equipment, what is the exact model, which listing does it carry, and do you have the manual and filter history?
Before you commit, run the dimensions through the doorway fit calculator and add the system to your kitchen equipment checklist. For broader inspection advice, read buying used restaurant equipment. You can browse used commercial cooking equipment or all restaurant equipment listings.
Seller checklist for listing a hood or ventless unit
- Hood type, manufacturer, model and serial number.
- Label photo and any listing mark (UL or ETL).
- Length, depth, height and weight if known.
- Appliances it served and cooking temperature rating.
- What's included, and what stays with the building.
- Fire suppression status and last service record, stated plainly. Don't claim it "will pass."
- Any modifications, dents or cut sections.
- Removal plan, rigging needs and pickup location.
- For ventless units, the exact listing and manual. Don't promise that no hood is needed, because the local authority decides.
Sellers can start at sell used restaurant equipment.
Sources
- International Code Council: 2021 IMC Chapter 5, Exhaust Systems and 2021 IMC Chapter 2, Definitions
- International Code Council: 2024 IMC Chapter 5, Exhaust Systems
- NFPA: NFPA 96 standard page
- NFPA: Restaurant Fire Protection Basics (blog, 2021)
- UL: Recirculating Hood Systems (PDF, 2006 newsletter article)
- San Francisco Department of Building Inspection: Information Sheet M-09 (PDF), including UL KNLZ and KNKG guide information
- City of Tucson: Kitchen Hood Requirements (PDF)
- City of Pittsburgh: Hood Requirements Related to Domestic Cooking Appliances (PDF)
- Minnesota Rules, part 1346.0507, via Cornell LII: Section 507 Commercial Kitchen Hoods
- TurboChef: Ventless Certification
- Greenheck: Kitchen Hoods, Type I and Type II, installation, operation and maintenance manual (PDF)
- CaptiveAire: VHB Type II hood, BD-2 Type I hood and NDI Type I hood (PDF)
- CaptiveAire: Recirculating hood FAQ and RH-2 recirculating hood manual (PDF)
Related guides
- Bar Equipment List: Underbar, Refrigeration and Glassware Checklist
A bar equipment list with maker specs for ice bins, bar sinks, glass washers, back bar coolers and draft, plus FDA Food Code items and used-buying checks.
- Coffee Shop Equipment List: What You Need, New or Used
A coffee shop equipment list with maker specs for espresso machines, grinders and brewers, utilities to plan first and what to check on used pieces.
- Commercial Refrigerator Sizes: Reach-In, Undercounter, Prep and Back Bar
Commercial refrigerator sizes from manufacturer spec sheets: reach-in, undercounter, chef base, prep and back bar dimensions, plus clearances and plugs.